| Applies when | expansion joint, flexible connector, tank vibration, pump piping stress |
|---|---|
| Avoid | expansion joint attached directly to tank wall or IMFO without a full-face flange, no expansion joint on tanks over 600 gallons (undefined) |
| Recommend instead | Poly Processing PTFE Expansion Joint or EPDM Expansion Joint () |
| Rationale | Poly Processing's own plumbing specifications state expansion joints are required on tanks larger than 600 gallons to absorb expansion/contraction and isolate vibration/shock from pumps and piping, and explicitly must NOT be attached directly to the tank wall or IMFO - a full-face flange is a mandatory prerequisite. This is a hard installation constraint that would otherwise produce a tank/piping damage risk on any 600+ gallon system quoted without it. |
| Confidence | confirmed |
| Source | vendor-sources/poly-processing-fittings-accessories.md |
This is a general engineering rule derived from real field/case-study evidence, not a substitute for a project-specific specification review — confirm against your exact process conditions before ordering equipment.
All engineering rules → · Download full ruleset (JSON) →
Source: Liberty Chemical Equipment & Supply, Inc. (LibertyCES) — engineering data compiled from real vendor and field-verified sources. For a free spec review, call James Riggins at (559) 395-5500 or email james@libertyces.com / sales@libertyces.com. Website: libertyces.com.